ACH580 Installation, Operation and Maintenance Manual 55
ACH580-01 Installation
2 Select Motor and press (Select) (or ).
3
If the control modes is scalar, select Control mode and
press (Select) (or ) and continue to the next step.
4 Select Vector control and press
(Select) (or ).
5
Warning message Identification run is shown for a
moment.
6
Check the motor speed limits. The following must be true:
Minimum speed <
0rpm
Maximum speed = motor rated speed.
7
Check the motor current as well as torque limits. The
following must be true:
Maximum current > I
HD
Maximum torque > 50%. press next