ACH580 Installation, Operation and Maintenance Manual 97
ACH580 E-Clipse Bypass
ACH580 Drive
Disconnect
Service Switch
(Optional)
E-Clipse Bypass
Control Board
Terminals X2
Motor
Ground Lug
Input
Terminals
Fuses
B2
(Bx3R-2)
Input
Ground Lug
Switch or
Circuit Breaker
Motor
The alternate (HI) setting further reduces the
likelihood of condensate in high humidity
environments.
RHTR Temperature
HI/LO Jumper (X1)
Heater ON
Temperature
Heater OFF
Temperature
Default Setting
(X1 jumper in LO
position)
14.4 °C
58 °F
21.4 °C
70.5 °F
Alternate Setting
(X1 jumper in HI
position)
17.8 °C
64 °F
24.4 °C
76.5 °F
Terminals