ACH580 E-Clipse bypass and packaged drive user manual 141
Embedded fieldbus
The system supports the following Modbus function codes for coils:
1xxxx Mapping – Modbus Discrete Inputs. The drive maps the following
information to the 1xxxx Modbus set called Modbus Discrete Inputs:
Bit-wise map of the
STATUS WORD (selected using bypass parameter 5825 EFB
CTRL PROFILE). The first 32 inputs are reserved for this purpose.
Discrete hardware inputs, numbered sequentially beginning with input 33.
The following table summarizes the 1xxxx reference set:
Function Code Description
01 Read coil status
05 Force single coil
15 (0x0F Hex) Force multiple coils
Modbus
Ref.
Internal Location
(All Profiles)
ABB DRV
BP Param
(5825 = 0 or 2)
DCU PROFILE
BP Param
(5825 = 1)
10001 STATUS WORD – Bit 0 RDY_ON READY
10002 STATUS WORD – Bit 1 RDY_RUN ENABLED
10003 STATUS WORD – Bit 2 RDY_REF STARTED
10004 STATUS WORD – Bit 3 TRIPPED RUNNING
10005 STATUS WORD – Bit 4 OFF_2_STA
1
ZERO_SPEED
10006 STATUS WORD – Bit 5 OFF_3_STA
1
ACCELERATE
10007 STATUS WORD – Bit 6 SWC_ON_INHIB DECELERATE
10008 STATUS WORD – Bit 7 WARNING AT_SETPOINT
10009 STATUS WORD – Bit 8 AT_SETPOINT LIMIT
10010 STATUS WORD – Bit 9 REMOTE SUPERVISION
10011 STATUS WORD – Bit 10 ABOVE_LIMIT REV_REF
10012 STATUS WORD – Bit 11 EXT2 REV_ACT
10013 STATUS WORD – Bit 12 RUN_ENABLE PANEL_LOCAL
10014 STATUS WORD – Bit 13 N/A FIELDBUS_LOCAL
10015 STATUS WORD – Bit 14 N/A EXT2_ACT
10016 STATUS WORD – Bit 15 N/A FAULT
10017 STATUS WORD – Bit 16 Reserved WARNING
10018 STATUS WORD – Bit 17 Reserved REQ_MAINT
10019 STATUS WORD – Bit 18 Reserved DIRLOCK
10020 STATUS WORD – Bit 19 Reserved LOCALLOCK
10021 STATUS WORD – Bit 20 Reserved CTL_MODE
10022 STATUS WORD – Bit 21 Reserved Reserved
10023 STATUS WORD – Bit 22 Reserved Reserved
10024 STATUS WORD – Bit 23 Reserved Reserved
10025 STATUS WORD – Bit 24 Reserved Reserved
10026 STATUS WORD – Bit 25 Reserved Reserved