13. Start-up the drive
WARNING! Obey these instructions. If you ignore them, injury or death, or damage to the equipment can occur. If
you are not a qualified electrical professional, do not do electrical installation or maintenance work.
Use the control panel to do the start-up procedure. The two commands at the bottom of the display show the functions of
the two softkeys and located below the display. The commands assigned to the softkeys are different
depending on the context. Use the arrow keys , , and to move the cursor or change values depending on the
active view. Key shows a context-sensitive help page.
1.
Power up the drive. Make sure that you
have the motor name plate data
available.
2.
Select the language you want to use
and press (OK).
Note: After you select the language, it
takes a few minutes for the control
panel to wake up.
3.
In the First start assistant screen,
select Exit and press (Next).
4.
In the Home screen, press
(Menu) to enter the Main Menu.
5.
In the Main menu, go to Parameters > Complete list > 95 HW configuration,
pressing
(Select) repeatedly to select parameter
95.01.
6.
In parameter 95.01 Supply voltage,
press (Edit).
Select supply voltage 380…415 V or
440…480 V and press (Save).
Go back to the Main menu by pressing
(Back) repeatedly.
In the Main menu, select First start
assistant and press (Select) to
enter the First start assistant menu.
Continue with the following steps for
commissioning the ACQ580.
7.
To complete the first start assistant,
select the values and settings when
prompted by the assistant. Continue
until the panel shows that the first
start is complete.
When the panel shows that the first
start is complete, the drive is ready for
use. Press (Done) to enter the
Home view.
8.
The Home view shows the values of the
selected signals.
9.
Make additional adjustments, for
example, pump protections, starting
from the Main menu. Press
(Menu) in the Home view to enter the
Main menu.
Select Primary settings and press
(Select) (or ).
To get more information on the
Primary settings menu items, press
to open the help page.
?
?