13
* These ratings are not to be used for drives with degree of protection of IP55 (UL Type 12) option +B056.
Terminal data
For tightening torques of grounding terminals, see section
Connect the power cables
.
* Maximum cable diameter accepted.
Notes:
The minimum specified wire size does not necessarily have sufficient current carrying capacity at maximum load. Make
sure the installation complies with local laws and regulations.
For IEC installations using mm
2
cable, the terminals do not accept a conductor that is one size larger than the
recommended wire size. For NEC installations using AWG cable, this applies only to the R8 frame 206A drive.
The maximum number of conductors per terminal is 1.
Dimensions, weights and free space requirements
200 mm (7.9 in) free space is required at top of the drive.
300 mm (11.8 in) free space (when measured from the drive base without the cable box) is required at bottom of the drive.
Ambient conditions
ACQ580
-31-…
NEC
ratings
Frame
size
Input rating Output ratings
Motor
power
1)
Fuses
3)
Typical
power cable
Typical
power loss
8)
UL class T
5)6)7)
Copper
I
1
I
2
I
Ld
P
Ld
Bussmann type
AWG
10)
W
AAAhp
U
n
= 3-phase 480 V
07A6-4 R3 7.0 7.6 7.6 5.0 JJS-15 14 219
012A-4 R3 9.0 12.0 12.0 7.5 JJS-20 14 278
014A-4 R3 12.0 14.0 14.0 10 JJS-25 14 321
023A-4 R3 17.0 23.0 23.0 15 JJS-35 10 473
027A-4 R6 24 27 27 20 JJS-40 8 625
034A-4 R6 29 34 34 25 JJS-50 8 711
044A-4 R6 34 44 44 30 JJS-60 6 807
052A-4 R6 44 52 52 40 JJS-80 4 960
065A-4* R6 54 65 65 50 JJS-90 2 1223
077A-4* R6 66 77 77 60 JJS-110 2 1560
096A-4 R8 82 96 96 75 JJS-150 1/0 1678
124A-4 R8 111 124 124 100 JJS-200 2/0 2237
156A-4 R8 134 156 156 125 JJS-225 4/0 2796
180A-4 R8 163 180 180 150 JJS-300 250 MCM 3356
Frame size
Cable entries L1, L2, L3, T1/U, T2/V, T3/W, UDC+ and UDC- terminals
pcs
Max. cable
diameter
*
Wire size Tightening torque
mm in mm
2
AWG N·m lbf·ft
R3 3 23 0.91 0.5…16.0 20…6 1.7 1.3
R6 3 45 1.77 6.0…70.0 10…2/0 5.6 4.1
R8 3 45 1.77 25…150 4…300MCM 30 22.5
Frame
size
Weight Height Width Depth
kg lb mm in mm in mm in
IP21, UL Type 1
R3 21.3 46.97 495 19.49 205 8.06 354 13.93
R6 61.0 134.51 771 30.35 252 9.91 393 15.46
R8 118 260.19 965 38.01 300 11.81 438 17.23
IP55, UL Type 12 (option +B056)
R3 21.3 46.97 490 19.29 205 8.06 360 14.17
R6 63.0 138.92 771 30.35 252 9.92 448 17.65
R8 124 273.42 965 37.99 300 11.81 496 19.53
Installation altitude 0 4000 m (0 13123 ft) above sea level. The output current must be derated at
altitudes above 1000 m (3281 ft). The derating is 1% for each 100 m (328 ft) above
1000 m (3281 ft).
Surrounding air temperature
Operation:
-15 +50 °C (5 122 °F). Frost is not permitted. The rated output current
must be derated by 1% for each 1 °C (1.8 °F) over 40 °C (104 °F). Storage (in the package):
-40 to +70 °C (-40 to +158 °F).