IEC RATINGS
Output ratingsMax cur-
rent
Input
rating
Frame
size
Drive
type
ACQ580-
34-…
Heavy-duty useLight-duty useNominal ratings
P
Hd
I
Hd
P
Ld
I
Ld
P
n
I
2
I
max
I
1
kWAkWAkWAAA
250505355618355650859569R11650A-4
IEC RATINGS
Output ratingsMax.
current
Input
rating
Frame
size
Drive
type
ACQ580-
34-
Heavy-duty useLight-duty useNominal ratings
P
Hd
I
Hd
P
Ld
I
Ld
P
n
I
2
I
max
I
1
hpAhpAhpAAA
U
n
= 480 V
150180200240200240350209R11246A-4
200240200260200260418233R11293A-4
250302300361300361498307R11365A-4
300361350414350414621363R11442A-4
300361350414350414631363R11505A-4
350414350430350430751389R11585A-4
350430400483400483859441R11650A-4
3AXD00000586715
UL (NEC) RATINGS
Output ratingsMax.
current
Input
rating
Frame
size
Drive
type
ACQ580-
34-
Heavy-duty useLight-duty useNominal ratings
P
Hd
I
Hd
P
Ld
I
Ld
P
n
I
2
I
max
I
1
hpAhpAhpAAA
U
n
= 480 V
150180200240200240350209R11240A-4
200240250302250302498258R11302A-4
250302300361300361542307R11361A-4
300361350414350414614363R11414A-4
350414400477400477704418R11477A-4
3AXD00000586715
Nominal voltage of the drive
U
n
Nominal input current (rms) at 40 °C (104 °F)
I
1
Maximum output current. Available for 10 seconds at start, otherwise as long as allowed by drive
temperature. 140% 200% of I
Hd
, depending on power rating.
I
max
Continuous rms output current. No overload capability at 40 °C (104 °F). This is indicated in the
type designation label as output current I
2
.
I
2
Typical motor power in no-overload use
P
n
Continuous rms output current allowing 10% overload for 1 minute every 10 minutes when parameter
97.02 Minimum switching frequency is set to 2 kHz or less.
I
Ld
166 Technical data

Table of Contents