Parameters 109
6
Parameters
What this chapter contains
The chapter describes the parameters, including actual signals, of the control
program.
Note: By default, a selective list of parameters is shown by the drive panel or
DriveStudio. All parameters can be displayed by setting parameter 16.21 Menu
selection to Full.
Terms and abbreviations
Term Definition
Actual signal Type of parameter that is the result of a measurement or calculation by
the drive. Actual signals can be monitored, but not adjusted, by the user.
Parameter groups 1…9 typically contain actual signals.
Bit pointer setting A parameter setting that points to the value of a bit in another parameter
(usually an actual signal), or that can be fixed to 0 (FALSE) or 1 (TRUE).
When adjusting a bit pointer setting on the optional control panel, “Const”
is selected in order to fix the value to 0 (displayed as C.False”) or 1
(“C.True”). “Pointer” is selected to define a source from another
parameter.
A pointer value is given in the format P.xx.yy.zz, where xx = parameter
group, yy = parameter index, zz = bit number.
Pointing to a nonexisting bit will be interpreted as 0 (FALSE).
In addition to the “Const” and “Pointer” selections, bit pointer settings may
also have other pre-selected settings.
FbEq Fieldbus equivalent. The scaling between the value shown on the panel
and the integer used in serial communication.
p.u. Per unit
Value pointer setting A parameter that points to the value of another actual signal or
parameter.
A pointer value is given in the format P.xx.yy, where xx = parameter
group, yy = parameter index.