Parameters 113
01.30 Polepairs Calculated number of pole pairs in the motor. 1 = 1
01.31 Mech time const Mechanical time constant of the drive and the machinery as
determined by the speed controller autotune function.
See parameter group 23 Speed ctrl on page 176.
1000 = 1 s
01.32 Temp phase A Measured temperature of phase U power stage in percent of
fault limit.
10 = 1%
01.33 Temp phase B Measured temperature of phase V power stage in percent of
fault limit.
10 = 1%
01.34 Temp phase C Measured temperature of phase W power stage in percent of
fault limit.
10 = 1%
01.35 Saved energy Energy saved in kWh compared to direct-on-line motor
connection.
Note: This value is derived from subtracting the drive’s
energy consumed from the direct-on-line consumption
calculated on the basis of parameter 45.08 Pump ref power.
As such, the accuracy of this signal is dependent on the
accuracy of the direct-on-line power estimate entered in that
parameter.
See parameter group 45 Energy optimising on page 227.
1 = 1 kWh
01.36 Saved amount Monetary savings compared to direct-on-line motor
connection. This value is a multiplication of parameters
01.35 Saved energy and 45.02 Energy tariff1.
See parameter group 45 Energy optimising on page 227.
100 = 1
01.37 Saved CO2 Reduction in CO
2
emissions in metric tons compared to
direct-on-line motor connection. This value is calculated by
multiplying the saved energy in MWh by 45.07 CO2 Conv
factor (default 0.5 tn/MWh).
See parameter group 45 Energy optimising on page 227.
10 = 1 metric
ton
01.38 Temp int board Measured temperature of the interface board in degrees
Celsius.
10 = 1 °C
02
02 I/O values
Input and output states and values; control and status words.
02.01 DI status Status of digital inputs DI6…DI1. Example: 000001 = DI1 is
on, DI2…DI6 are off.
-
02.02 RO status Status of relay outputs RO5…RO1. Example: 00001 = RO1
is energized, RO2…RO5 are de-energized.
-
02.03 DIO status Status of digital input/outputs DIO4…DIO1. Example:
0000001001 = DIO1 and DIO4 are on, remainder are off.
DIO3…DIO4 are available only with an FIO I/O extension
module.
-
02.04 AI1 Value of analog input AI1 in V or mA. Input type is selected
with a jumper on the JCU Control Unit.
1000 = 1 unit
02.05 AI1 scaled Scaled value of analog input AI1. See parameters 13.04 AI1
max scale and 13.05 AI1 min scale.
1000 = 1 unit
02.06 AI2 Value of analog input AI2 in V or mA. Input type is selected
with a jumper on the JCU Control Unit.
1000 = 1 unit
02.07 AI2 scaled Scaled value of analog input AI2. See parameters 13.09 AI2
max scale and 13.10 AI2 min scale.
1000 = 1 unit
02.08 AI3 Value of analog input AI3 in V or mA. For input type
information, see the extension module manual.
1000 = 1 unit
02.09 AI3 scaled Scaled value of analog input AI3. See parameters 13.14 AI3
max scale and 13.15 AI3 min scale.
1000 = 1 unit