Parameters 131
06.22 MF status word Multipump communication status word. -
08
08 Alarms & faults
Alarm and fault information.
08.01 Active fault Fault code of the latest fault. 1 = 1
08.02 Last fault Fault code of the 2nd latest fault. 1 = 1
08.03 Fault time hi Time (real time or power-on time) at which the active fault
occurred in format dd.mm.yy (day, month and year).
1 = 1 d
08.04 Fault time lo Time (real time or power-on time) at which the active fault
occurred in format hh.mm.ss (hours, minutes and seconds).
1 = 1
08.05 Alarm word1 Alarm word 1. Can be reset by entering a 0. -
No. Name/Value Description FbEq
Bit Name Value Information
0 Master 1 Drive is master.
1 Follower 1 Drive is follower.
2 Master running 1 Master drive is running.
3 Copy of mstr 1 Sync mode active (par. 75.03 is set to Copy of mstr).
4 Node 1 1 (Only valid if the drive is master.) Drive with node number 1 is
present on the drive-to-drive link.
5 Node 2 1 (Only valid if the drive is master.) Drive with node number 2 is
present on the drive-to-drive link.
6 Node 3 1 (Only valid if the drive is master.) Drive with node number 3 is
present on the drive-to-drive link.
7 Node 4 1 (Only valid if the drive is master.) Drive with node number 4 is
present on the drive-to-drive link.
8 Node 5 1 (Only valid if the drive is master.) Drive with node number 5 is
present on the drive-to-drive link.
9 Node 6 1 (Only valid if the drive is master.) Drive with node number 6 is
present on the drive-to-drive link.
10 Node 7 1 (Only valid if the drive is master.) Drive with node number 7 is
present on the drive-to-drive link.
11 Node 8 1 (Only valid if the drive is master.) Drive with node number 8 is
present on the drive-to-drive link.
12…31 Reserved
Bit Name
0…2 Reserved
3 SAFE TORQUE OFF (page 314)
4 STO MODE CHANGE (page 314)
5 MOTOR TEMPERATURE (page 314)
6 EMERGENCY OFF (page 314)
7 RUN ENABLE (page 314)
8 ID-RUN (page 315)
9 EMERGENCY STOP (page 315)
10…12 Reserved
13 DEVICE OVERTEMP (page 315)
14 INTBOARD OVERTEMP (page 315)
15 Reserved