Parameters 135
09.10 Int logic ver Displays the version of the logic on the main circuit board of
the drive.
-
09.20 Option slot1 Displays the type of the optional module in option slot 1.
0 = No option, 1 = No comm, 2 = Unknown, 6 = FIO-01,
7 = FIO-11, 8 = FPBA-01, 9 = FPBA-02, 10 = FCAN-01,
11 = FDNA-01, 12 = FENA-01, 13 = FENA-02,
14 = FLON-01, 15 = FRSA-00, 16 = FMBA-01,
17 = FFOA-01, 18 = FFOA-02, 19 = FSEN-01, 21 = FIO-21,
22 = FSCA-01, 23 = FSEA-21, 24 = FIO-31, 25 = FECA-01
1 = 1
09.21 Option slot2 Displays the type of the optional module in option slot 2. See
09.20 Option slot1.
1 = 1
10
10 Start/stop/dir
Start/stop/direction, run enable and emergency stop source
selections; start inhibit and start interlock configuration.
10.01 Ext1 start func Selects the source of start and stop commands for external
control location 1 (EXT1).
Note: This parameter cannot be changed while the drive is
running.
Not sel No start or stop command sources selected. 0
In1 The source of the start and stop commands is selected by
parameter 10.02 Ext1 start in1. The state transitions of the
source bit are interpreted as follows:
1
3-wire The sources of the start and stop commands is selected by
parameters 10.02 Ext1 start in1 and 10.03 Ext1 start in2.
The state transitions of the source bits are interpreted as
follows:
2
FBA The start and stop commands are taken from the fieldbus
Control Word selected by parameter 50.15 Fb cw used.
3
D2D Reserved. 4
In1F In2R The source selected by 10.02 Ext1 start in1 is the forward
start signal, the source selected by 10.03 Ext1 start in2 is the
reverse start signal.
5
No. Name/Value Description FbEq
State of source
(via par 10.02)
Command
0
-
> 1 Start
1
-
> 0 Stop
State of source 1
(via par. 10.02)
State of source 2
(via par. 10.03)
Command
0
-
> 1 1 Start
Any 1
-
> 0 Stop
Any 0 Stop
State of source 1
(via par. 10.02)
State of source 2
(via par. 10.03)
Command
00Stop
1 0 Start forward
0 1 Start reverse
11Stop