Parameters 137
FBA The start and stop commands are taken from the fieldbus
Control Word selected by parameter 50.15 Fb cw used.
3
D2D Reserved. 4
In1F In2R The source selected by 10.05 Ext2 start in1 is the forward
start signal, the source selected by 10.06 Ext2 start in2 is the
reverse start signal.
5
In1St In2Dir The source selected by 10.05 Ext2 start in1 is the start signal
(0 = stop, 1 = start), the source selected by 10.06 Ext2 start
in2 is the direction signal (0 = forward, 1 = reverse).
6
10.05 Ext2 start in1 Selects source 1 of start and stop commands for external
control location EXT2. See parameter 10.04 Ext2 start func,
selections In1 and 3-wire.
Note: This parameter cannot be changed while the drive is
running.
DI1 Digital input DI1 (as indicated by 02.01 DI status, bit 0). 1073742337
DI2 Digital input DI2 (as indicated by 02.01 DI status, bit 1). 1073807873
DIO4 Digital input/output DIO4 (as indicated by 02.03 DIO status,
bit 3).
1073938947
Timed func Bit 4 of parameter 06.14 Timed func stat. The bit is on when
any one of the four timers configured in parameter group 36
Timed functions is on.
1074005518
Const Bit pointer setting (see Terms and abbreviations on page
109).
-
Pointer
10.06 Ext2 start in2 Selects source 2 of start and stop commands for external
control location EXT2. See parameter 10.04 Ext2 start func,
selection 3-wire.
Note: This parameter cannot be changed while the drive is
running.
DI2 Digital input DI2 (as indicated by 02.01 DI status, bit 1). 1073807873
DI5 Digital input DI5 (as indicated by 02.01 DI status, bit 4). 1074004481
Const Bit pointer setting (see
Terms and abbreviations on page
109).
-
Pointer
10.10 Fault reset sel Selects the source of the external fault reset signal. The
signal resets the drive after a fault trip if the cause of the fault
no longer exists.
0 -> 1 = Fault reset.
DI1 Digital input DI1 (as indicated by 02.01 DI status, bit 0). 1073742337
DI2 Digital input DI2 (as indicated by 02.01 DI status, bit 1). 1073807873
DI3 Digital input DI3 (as indicated by 02.01 DI status, bit 2). 1073873409
DI4 Digital input DI4 (as indicated by 02.01 DI status, bit 3). 1073938945
DI5 Digital input DI5 (as indicated by 02.01 DI status, bit 4). 1074004481
No. Name/Value Description FbEq
State of source 1
(via par. 10.05)
State of source 2
(via par. 10.06)
Command
00Stop
1 0 Start forward
0 1 Start reverse
11Stop