148 Parameters
Last speed The drive generates an AI SUPERVISION (0x8110) alarm
and freezes the speed to the level the drive was operating at.
The speed is determined by the average speed over the
previous 10 seconds.
WARNING! Make sure that it is safe to continue
operation in case of a communication break.
3
13.33 AI superv cw Selects the analog input signal supervision limit.
Example: If parameter value is set to 0b0010, bit 1 AI1 max
sup is selected.
14
14 Digital I/O
Configuration of digital input/outputs, relay outputs, the
frequency input, and the frequency output.
14.01 DI invert mask Inverts status of digital inputs as reported by 02.01 DI status.
14.02 DIO1 conf Selects whether DIO1 is used as a digital output or input.
Output DIO1 is used as a digital output. 0
Input DIO1 is used as a digital input. 1
Freq input DIO1 is used as a frequency input. 2
14.03 DIO1 out src Selects a drive signal to be connected to digital output DIO1
(when 14.02 DIO1 conf is set to Output).
Trad pump7 Bit 6 of 05.02 Trad pump cmd (see page 125). 1074136322
Trad pump8 Bit 7 of 05.02 Trad pump cmd (see page 125). 1074201858
Ready Bit 0 of 06.01 Status word1 (see page 126). 1073743361
Enabled Bit 1 of 06.01 Status word1 (see page 126). 1073808897
Started Bit 2 of 06.01 Status word1 (see page 126). 1073874433
Running Bit 3 of 06.01 Status word1 (see page 126). 1073939969
Alarm Bit 7 of 06.01 Status word1 (see page 126). 1074202113
Ext2 active Bit 8 of 06.01 Status word1 (see page 126). 1074267649
Fault Bit 10 of 06.01 Status word1 (see page 126). 1074398721
No. Name/Value Description FbEq
Bit Supervision Action selected by parameter 13.32 AI superv func is taken if
0 AI1 min sup AI1 signal value falls below the value defined by equation: par. 13.03
AI1 min - 0.5 mA or V
1 AI1 max sup AI1 signal value exceeds the value defined by equation: par. 13.02
AI1 max + 0.5 mA or V
2 AI2 min sup AI2 signal value falls below the value defined by equation: par. 13.08
AI2 min - 0.5 mA or V
3 AI2 max sup AI1 signal value exceeds the value defined by equation: par. 13.07
AI2 max + 0.5 mA or V
Bit Name
0 1 = Invert DI1
1 1 = Invert DI2
2 1 = Invert DI3
3 1 = Invert DI4
4 1 = Invert DI5