Parameters 167
M lvl short A selective list of parameters relevant to the Level control
application macro (multipump) is displayed.
11
M lvl long A more comprehensive list of parameters relevant to the
Level control application macro (multipump) is displayed.
12
M pump short A selective list of parameters relevant to the Multipump
control application macro (single-pump) is displayed.
13
M pump long A more comprehensive list of parameters relevant to the
Multipump control application macro (single-pump) is
displayed.
14
Full All parameters are displayed. 15
16.17 Power unit Selects the unit of power for parameters such as 01.22
Power inu out, 01.23 Motor power and 99.10 Mot nom
power.
kW Kilowatt. 0
hp Horsepower. 1
16.20 Macro selected Shows which application macro is currently selected. For
more information, see chapter Application macros (page 87).
Note: Changing the value of this parameter does not change
the current application macro. To change the application
macro, use the Application macro assistant available
through the control panel instead.
Factory def Factory default macro. 0
Ext ctrl External control macro. 1
Trad ctrl Traditional pump control macro. 2
Hand/Auto Hand/Auto macro. 3
Level ctrl Level control macro (for a single pump). 4
Multi level Level control macro (for multiple pumps). 5
Multi pump Multipump control macro. 6
16.21 Menu selection Loads a short, long or full parameter list.
Short Only a selective list of parameters will be displayed. 0
Long Only the parameters relevant to the current application
macro are displayed.
1
Full All parameters are displayed, including those not relevant to
the current application macro.
2
19
19 Speed calculation
Speed scaling, feedback and supervision settings.
19.01 Speed scaling Defines the terminal speed value used in acceleration and
the initial speed value used in deceleration (see parameter
group 22 Speed ref ramp). Also defines the rpm value that
corresponds to 20000 for fieldbus communication with ABB
Drives communication profile.
0 … 30000 rpm Acceleration/deceleration terminal/initial speed. 1 = 1 rpm
19.02 Speed fb sel Selects the speed feedback value used in control.
Note: The speed feedback value is always estimated.
Estimated A calculated speed estimate is used. 0
No. Name/Value Description FbEq