174 Parameters
22.03 Dec time Defines deceleration time as the time required for the speed
to change from the speed value defined by parameter 19.01
Speed scaling to zero.
If the speed reference decreases slower than the set
deceleration rate, the motor speed will follow the reference
signal.
If the reference changes faster than the set deceleration
rate, the motor speed will follow the deceleration rate.
If the deceleration time is set too short, the drive will
automatically prolong the deceleration in order not to exceed
drive torque limits. If there is any doubt about the
deceleration time being too short, ensure that the DC
overvoltage control is on (parameter 47.01 Overvolt ctrl).
0.000 … 1800.000 s Deceleration time. 1000 = 1 s