Parameters 187
DI3 Digital input DI3 (as indicated by 02.01 DI status, bit 2). 1073873409
DI4 Digital input DI4 (as indicated by 02.01 DI status, bit 3). 1073938945
DI5 Digital input DI5 (as indicated by 02.01 DI status, bit 4). 1074004481
Const Bit pointer setting (see Terms and abbreviations on page
109).
-
Pointer
26.06 Const speed1 Defines constant speed 1.
-30000 … 30000
rpm
Constant speed 1. 1 = 1 rpm
26.07 Const speed2 Defines constant speed 2.
-30000 … 30000
rpm
Constant speed 2. 1 = 1 rpm
26.08 Const speed3 Defines constant speed 3.
-30000 … 30000
rpm
Constant speed 3. 1 = 1 rpm
26.09 Const speed4 Defines constant speed 4.
-30000 … 30000
rpm
Constant speed 4. 1 = 1 rpm
26.10 Const speed5 Defines constant speed 5.
-30000 … 30000
rpm
Constant speed 5. 1 = 1 rpm
26.11 Const speed6 Defines constant speed 6.
-30000 … 30000
rpm
Constant speed 6. 1 = 1 rpm
26.12 Const speed7 Defines constant speed 7.
-30000 … 30000
rpm
Constant speed 7. 1 = 1 rpm
27
27 Process PID
Configuration of process PID control.
See also section PID control on page 58.
27.01 PID setpoint sel Selects the source of setpoint (reference) for the PID
controller.
Zero Zero reference. 0
Setpoint % 04.25 Setpoint val % (see page 124). 1073742873
Pointer Value pointer setting (see Terms and abbreviations on page
109).
-
27.12 PID gain Defines the gain for the process PID controller. See
parameter 27.13 PID integ time.
0.00 … 100.00 Gain for PID controller. 100 = 1
No. Name/Value Description FbEq