Parameters 205
Process act 04.01 Act val (see page 123). 1073742849
Proc PID out 04.05 Process PID out (see page 123). 1073742853
Pointer Value pointer setting (see Terms and abbreviations on page
109).
-
33.11 Superv3 hi Selects the upper limit for supervision 3. See parameter
33.09 Superv3 func.
-32768.00 …
32768.00
Upper limit for supervision 3. 100 = 1
33.12 Superv3 lo Selects the lower limit for supervision 3. See parameter
33.09 Superv3 func.
-32768.00 …
32768.00
Lower limit for supervision 3. 100 = 1
34
34 User load curve
Configuration of user load curve.
See also section User-definable load curve on page 71.
34.01 Overload func Configures the supervision of the upper boundary of the user
load curve.
No. Name/Value Description FbEq
Bit Function
0
Ena sup (Enable supervision)
0 = Disabled: Supervision disabled.
1 = Enabled: Supervision enabled.
1
Input value sel (Input value selection)
0 = Current: Current is supervised.
1 = Torque: Torque is supervised.
2
Ena warn (Enable warning)
0 = Disabled
1 = Enabled: Drive generates alarm LCURVE (0x2312) when the curve is exceeded.
3
Ena fault (Enable fault)
0 = Disabled
1 = Enabled: Drive trips on fault LOAD CURVE (0x2312) when the curve is exceeded.
4
Ena lim integ (Enable limit integration)
0 = Disabled
1 = Enabled: Integration time defined by parameter 34.18 Load integ time is used. After
the supervision is evoked, the current or torque is limited by the upper boundary of the
load curve.
5
Ena lim always (Enable limit always)
0 = Disabled
1 = Enabled: The current or torque is always limited by the upper boundary of the load
curve.