228 Parameters
45.09 Energy reset Resets the energy counters 01.35 Saved energy, 01.36
Saved amount and 01.37 Saved CO2.
Done Reset not requested (normal operation). 0
Reset Reset energy counters. The value reverts automatically to
Done.
1
47
47 Voltage ctrl
Overvoltage and undervoltage control settings.
See also DC voltage control on page 76.
47.01 Overvolt ctrl Enables the overvoltage control of the intermediate DC link.
Fast braking of a high inertia load causes the voltage to rise
to the overvoltage control limit. To prevent the DC voltage
from exceeding the limit, the overvoltage controller
automatically decreases the braking torque.
Disable Overvoltage control disabled. 0
Enable Overvoltage control enabled. 1
47.02 Undervolt ctrl Enables the undervoltage control of the intermediate DC link.
If the DC voltage drops due to input power cut off, the
undervoltage controller will automatically decrease the motor
torque in order to keep the voltage above the lower limit. By
decreasing the motor torque, the inertia of the load will
cause regeneration back to the drive, keeping the DC link
charged and preventing an undervoltage trip until the motor
coasts to stop. This will act as a power-loss ride-through
functionality in systems with high inertia.
Disable Undervoltage control disabled. 0
Enable Undervoltage control enabled. 1
47.03 SupplyVoltAutoId Enables the auto-identification of the supply voltage.
Disable Auto-identification of supply voltage disabled. 0
Enable Auto-identification of supply voltage enabled. 1
47.04 Supply voltage Defines the nominal supply voltage. Used if auto-
identification of the supply voltage is not enabled by
parameter 47.03 SupplyVoltAutoId.
0 … 1000 V Nominal supply voltage. 10 = 1 V
49
49 Data storage
Data storage parameters reserved for the user.
These parameters can be written to and read from using
other parameters’ pointer settings. Four 16-bit and four 32-
bit storage parameters are available.
49.01 Data storage1 Data storage parameter 1.
-32768 … 32767 16-bit data. 1 = 1
49.02 Data storage2 Data storage parameter 2.
-32768 … 32767 16-bit data. 1 = 1
49.03 Data storage3 Data storage parameter 3.
-32768 … 32767 16-bit data. 1 = 1
49.04 Data storage4 Data storage parameter 4.
-32768 … 32767 16-bit data. 1 = 1
49.05 Data storage5 Data storage parameter 5.
-2147483647 …
2147483647
32-bit data. 1 = 1