Parameters 231
50.20 Fb main sw func Selects the rule on the basis of which the drive defines the
value for 02.24 FBA main sw bit 1 (Enabled).
51
51 FBA settings
Fieldbus adapter-specific settings.
51.01 FBA type Displays the type of the connected fieldbus adapter module.
0 = Fieldbus module is not found, or it is not properly
connected, or parameter 50.01 FBA enable is set to Disable,
1 = PROFIBUS DP, 32 = CANopen, 37 = DeviceNet,
128 = Ethernet, 132 = PROFINET IO, 135 = EtherCAT,
136 = Ethernet POWERLINK, 485 = RS-485,
62944 = SERCOS interface.
51.02 FBA par2 Parameters 51.0251.26 are adapter module-specific. For
more information, see the Users Manual of the fieldbus
adapter module. Note that not all of these parameters are
necessarily used.
-
……
51.26 FBA par26 See parameter 51.02 FBA par2.-
51.27 FBA par refresh Validates any changed adapter module configuration
parameter settings. After refreshing, the value reverts
automatically to Done.
Note: This parameter cannot be changed while the drive is
running.
Done Refreshing done. 0
Refresh Refreshing. 1
51.28 Par table ver Displays the parameter table revision of the fieldbus adapter
module mapping file stored in the memory of the drive.
In format xyz, where x = major revision number; y = minor
revision number; z = correction number.
0x0000 … 0xFFFF Parameter table revision. 1 = 1
51.29 Drive type code Displays the drive type code of the fieldbus adapter module
mapping file stored in the memory of the drive.
0 … 65535 Drive type code of fieldbus adapter module mapping file. 1 = 1
51.30 Mapping file ver Displays the fieldbus adapter module mapping file revision
stored in the memory of the drive in decimal format.
Example: 0x107 = revision 1.07.
0 … 65535 Mapping file revision. 1 = 1
51.31 D2FBA comm sta Displays the status of the fieldbus adapter module
communication.
Idle Adapter is not configured. 0
Exec.init Adapter is initializing. 1
No. Name/Value Description FbEq
Bit Name Information
0
Run enable
func
1 = Parameter only:
Drive writes value 1 to the bit when the external run enable signal (par.
10.11 Run enable) has value 1.
0 = Param AND Fb cw:
Drive writes value 1 to the bit when the external run enable signal (par.
10.11 Run enable) is 1 AND 02.22 FBA main cw bit 7 (Run enable) is 1.