248 Parameters
The following diagram shows the order of some common
speeds in a pump application.
0…32767 rpm Start speed for auxiliary pump 1. 1 = 1 rpm
75.06 Start speed 2 Defines the start speed for auxiliary pump 2. See parameter
75.05 Start speed 1.
0…32767 rpm Start speed for auxiliary pump 2. 1 = 1 rpm
75.07 Start speed 3 Defines the start speed for auxiliary pump 3. See parameter
75.05 Start speed 1.
0…32767 rpm Start speed for auxiliary pump 3. 1 = 1 rpm
75.08 Start speed 4 Defines the start speed for auxiliary pump 4. See parameter
75.05 Start speed 1.
0…32767 rpm Start speed for auxiliary pump 4. 1 = 1 rpm
75.09 Start speed 5 Defines the start speed for auxiliary pump 5. See parameter
75.05 Start speed 1.
0…32767 rpm Start speed for auxiliary pump 5. 1 = 1 rpm
75.10 Start speed 6 Defines the start speed for auxiliary pump 6. See parameter
75.05 Start speed 1.
0…32767 rpm Start speed for auxiliary pump 6. 1 = 1 rpm
75.11 Start speed 7 Defines the start speed for auxiliary pump 7. See parameter
75.05 Start speed 1.
0…32767 rpm Start speed for auxiliary pump 7. 1 = 1 rpm
No. Name/Value Description FbEq
0 rpm
27.19 PID minimum
77.03 Sleep level
75.12 Stop speed 1 (Stop speed of auxiliary pump 1)
Speed
75.05 Start speed 1 (Start speed of auxiliary pump 1)
20.01 Maximum speed
20.02 Minimum speed
(Negative speeds only used by the pump cleaning function (82.03)