Parameters 261
Const Bit pointer setting (see Terms and abbreviations on page
109).
-
Pointer
78.11 Interlock pump 6 Selects the input (or signal) for status of pump 6.
When the input is 1, the drive assumes the pump is in use
and can be started.
Not used The interlock is off, meaning that the pump is not in use. 0
On The interlock is on, meaning that the pump is ready for use. 1
DI1 Digital input DI1 (as indicated by 02.01 DI status, bit 0). 1073742337
DI2 Digital input DI2 (as indicated by 02.01 DI status, bit 1). 1073807873
DI3 Digital input DI3 (as indicated by 02.01 DI status, bit 2). 1073873409
DI4 Digital input DI4 (as indicated by 02.01 DI status, bit 3). 1073938945
DI5 Digital input DI5 (as indicated by 02.01 DI status, bit 4). 1074004481
Const Bit pointer setting (see Terms and abbreviations on page
109).
-
Pointer
78.12 Interlock pump 7 Selects the input (or signal) for status of pump 7.
When the input is 1, the drive assumes the pump is in use
and can be started.
Not used The interlock is off, meaning that the pump is not in use. 0
On The interlock is on, meaning that the pump is ready for use. 1
DI1 Digital input DI1 (as indicated by 02.01 DI status, bit 0). 1073742337
DI2 Digital input DI2 (as indicated by 02.01 DI status, bit 1). 1073807873
DI3 Digital input DI3 (as indicated by 02.01 DI status, bit 2). 1073873409
DI4 Digital input DI4 (as indicated by 02.01 DI status, bit 3). 1073938945
DI5 Digital input DI5 (as indicated by 02.01 DI status, bit 4). 1074004481
Const Bit pointer setting (see Terms and abbreviations on page
109).
-
Pointer
78.13 Interlock pump 8 Selects the input (or signal) for status of pump 8.
When the input is 1, the drive assumes the pump is in use
and can be started.
Not used The interlock is off, meaning that the pump is not in use. 0
On The interlock is on, meaning that the pump is ready for use. 1
DI1 Digital input DI1 (as indicated by 02.01 DI status, bit 0). 1073742337
DI2 Digital input DI2 (as indicated by 02.01 DI status, bit 1). 1073807873
DI3 Digital input DI3 (as indicated by 02.01 DI status, bit 2). 1073873409
DI4 Digital input DI4 (as indicated by 02.01 DI status, bit 3). 1073938945
DI5 Digital input DI5 (as indicated by 02.01 DI status, bit 4). 1074004481
Const Bit pointer setting (see Terms and abbreviations on page
109).
-
Pointer
78.14 Runtime change Enables the reset, or arbitrary setting, of 04.28 Pump
runtime.
No The parameter automatically reverts to this value. 0
Set Enables the setting of 04.28 Pump runtime to an arbitrary
value.
1
No. Name/Value Description FbEq