268 Parameters
Pointer Value pointer setting (see Terms and abbreviations on page
109).
-
80.03 Pump outlet sel Selects the analog input (or other signal source) used for
pump outlet pressure measurement.
Zero No input selected (no pressure sensor available). 0
AI1 scaled 02.05 AI1 scaled (see page 113 ). 1073742341
AI2 scaled 02.07 AI2 scaled (see page 113 ). 1073742343
AI3 scaled 02.09 AI3 scaled (see page 113 ). 1073742345
AI4 scaled 02.11 AI4 scaled (see page 11 4 ). 1073742347
AI5 scaled 02.13 AI5 scaled (see page 114 ). 1073742349
Pointer Value pointer setting (see Terms and abbreviations on page
109).
-
80.04 HQ curve Q1 Flow rate (in cubic meters per hour) at point 1 of the HQ
performance curve.
Parameters 80.0480.13 define the HQ performance curve
of the pump for the flow calculation function. The H (head, or
level) and Q (flow rate) coordinates of five points on the
curve are entered. The values are provided by the pump
manufacturer. All points defined should lie within the
practical operating range of the pump.
Below is an example of an HQ performance curve. The
defining parameters of the first and last points are shown.
0.00 … 32767.00
m
3
/h
Flow rate at point 1 of the HQ curve. 100 = 1 m
3
/h
80.05 HQ curve H1 Head (in meters) at point 1 of the HQ performance curve.
0.00 … 32767.00 m Head at point 1 of the HQ curve. 100 = 1 m
80.06 HQ curve Q2 Flow rate (in cubic meters per hour) at point 2 of the HQ
performance curve.
0.00 … 32767.00
m
3
/h
Flow rate at point 2 of the HQ curve. 100 = 1 m
3
/h
No. Name/Value Description FbEq
H [m]
Q [m
3
/h]
80.05
80.13
2
4
5
3
1
80.0480.12