66 Program features
Diagnostics
Parameters 02.01 DI status (page 113 ), 02.03 DIO status (page 113), 02.20 Freq in
(page 114) and 02.21 Freq out (page 114).
Programmable I/O extensions
The number of inputs and outputs can be increased by using FIO-xx I/O extensions.
The drive I/O configuration parameters include the maximum number of DI, DIO, AI,
AO and RO that can be taken into use with different FIO-xx combinations.
The table below shows the possible I/O combinations of the drive:
For example, with an FIO-21 connected to the drive, parameters controlling DI1…7,
DIO1…4, AI1…3, AO1…2 and RO1…4 are in use.
Settings
Parameter groups 13 Analogue inputs (page 142), 14 Digital I/O (page 148), 15
Analogue outputs (page 158) and 94 Ext IO conf (page 281).
Programmable relay outputs
The drive has two relay outputs. The signals to be indicated by the outputs can be
selected by parameters.
Relay outputs can be added by using FIO-xx I/O extensions.
Settings
Parameter group 14 Digital I/O (page 148).
Diagnostics
Parameter 02.02 RO status (page 113 ).
Fieldbus control
The drive can be connected to several different automation systems through its
fieldbus interface. See chapters Control through the embedded fieldbus interface
(page 329) and Control through a fieldbus adapter (page 357).
Digital
inputs
(DI)
Digital I/O
(DIO)
Analog
inputs
(AI)
Analog
outputs
(AO)
Relay
outputs
(RO)
JCU Control Unit62222
FIO-11 - 2 3 1 -
FIO-21 1-1-2
FIO-31 ----4