Technical data 109
Fuse tables
gG fuses
Drive type
ACq810-04…
Input
current
Min.
short-
circuit
current
1)
Fuse
AAA
A
2
s
V Manufacturer Type IEC
size
-302A-4 297 8280 500 2 900 000 500 ABB Control OFAF3H500 3
-361A-4 355 8280 500 2 900 000 500 ABB Control OFAF3H500 3
-414A-4 407 8280 500 2 900 000 500 ABB Control OFAF3H500 3
-477A-4 459 10200 630 4 000 000 500 ABB Control OFAF3H630 3
-550A-4 531 10200 630 4 000 000 500 ABB Control OFAF3H630 3
-616A-4 599 13500 800 7 400 000 500 ABB Control OFAF3H800 3
-704A-4 689 13500 800 7 400 000 500 ABB Control OFAF3H800 3
1)
minimum short-circuit current of the installation
Note 1: See also Implementing thermal overload and short-circuit protection on page 62. For UL recognized
fuses, see Fuses (UL) on page 110.
Note 2: In multicable installations, install only one fuse per phase (not one fuse per conductor).
Note 3: Larger fuses than the recommended ones must not be used.
Note 4: Fuses from other manufacturers can be used if they meet the ratings and the melting curve of the
fuse does not exceed the melting curve of the fuse mentioned in the table.
00581898, 00581898
Ultrarapid (aR) fuses
Drive type
ACS800-04…
Input
current
A
Min.
short-
circuit
current
1)
Fuse
AA
A
2
s
V Manufacturer Type DIN
43620
Size
-302A-4 297 4000 800 465 000 690 Bussmann 170M6812 DIN2*
-361A-4 355 4000 800 465 000 690 Bussmann 170M6812 DIN2*
-414A-4 407 4000 800 465 000 690 Bussmann 170M6812 DIN2*
-477A-4 459 7800 1250 1 950 000 690 Bussmann 170M8554 DIN3
-550A-4 531 7800 1250 1 950 000 690 Bussmann 170M8554 DIN3
-616A-4 599 8850 1400 3 900 000 690 Bussmann 170M8555 DIN3
-704A-4 689 8850 1400 3 900 000 690 Bussmann 170M8555 DIN3
1)
minimum short-circuit current of the installation
Note 1: See also Implementing thermal overload and short-circuit protection on page 62. For UL recognized
fuses, see Fuses (UL) on page 110.
Note 2: In multicable installations, install only one fuse per phase (not one fuse per conductor).
Note 3: Larger fuses than the recommended ones must not be used.
Note 4: Fuses from other manufacturers can be used if they meet the ratings and the melting curve of the
fuse does not exceed the melting curve of the fuse mentioned in the table.