32 Planning the cabinet installation
Planning the layout of the cabinet
Design a spacious layout to ensure easy installation and maintenance. Sufficient cooling
air flow, obligatory clearances, cables and cable support structures all require space.
Place the control board(s) away from:
the main circuit components such as contactor, switches and power cables
hot parts (heat sink, air outlet of the drive module).
Layout examples, door closed
Layout examples for IP22 and IP54 cabinets are shown below.
1a Air inlet for the drive module
1b Air inlet for the other equipment
2a Air outlet for the drive module
2b Air outlet for the other
equipment
2c Air outlet for the drive module
and the other equipment, an
extra exhaust fan
3 Drive control panel (control
panel door mounting kit,
+J410). The control panel is
connected to the JCU Control
Unit inside the cabinet)
4 Contactor control switch and
emergency stop switch
(connected to the contactor
control circuit inside the
cabinet)
5 Operating handle of the
disconnector
4
5
1a
1b
IP54
4
5
1a
1b
1a
IP22
2c
2b
1a
2a
Roof air flow viewed from top
3
3