60 ACS 300 User’s Manual
Chapter 7 - Drive Parameters
apply the analogue input signal that represents minimum
frequency in your system. Press and hold the key for three
seconds. The setting is accepted when * blinks once on the
Control Panel display. To set the maximum reference signal level,
scroll to SET MAX and repeat the procedure as for SET MIN.
Note! The drive will stop, a fault message “LOW AI-SIGNAL”
appears and the fault LED lights if parameter AI-FAULT (refer to
page 67) has been enabled and the reference drops below the
selected minimum limit.
Figure 7-3 Customised minimum and maximum limits for the
reference input.
A. OUT
This parameter selects which signal is connected to analogue
output.
NONE– Analogue output is 0 mA.
OUT FREQOutput frequency (0 to the selected maximum
frequency)
REF FREQ– Reference frequency (0 to the selected maximum
frequency)
MOTOR CUR– Motor current (0 to 1.5 x I
N
, see Table 1-1 and
Table 1-2)
Hysteresis
2 %
Output frequency
Analogue Input
MAX FREQ
MIN FREQ
0
CUSTOM
MIN
CUSTOM
MAX
10 v/ 20mA
(100%)