80 ACS 300 User’s Manual
Chapter 8 - Fault Tracing
(6) PANEL COM ERR Control Panel was removed
when control was in Local mode.
Due to safety reasons, the drive
stops in this fault condition.
Attach the Control Panel and
reset the fault, then change to
Remote mode and remove
Panel.
Use remote (wired) controls to
reset the fault, then start and
run with remote controls
There might be a loose contact.
Check the panel connection.
(10) BUS COMM FLT Bus communication error Check bus connections
(7) UNIT FAULT ACS 300 heatsink temperature
too high.
CHECK:
Heatsink dissipation
Dust and dirt
Air flow
•Fan
Ambient temperature
Reduce switching frequency.
Check load current
Earth faults or short circuits. CHECK:
Terminals
•Motor
Cables
With frame size R2 high load
inertia / short ramp
CHECK:
Ramps times
Remove mechanical problems
Dimensioning
(8) UNIT FAULT Inverter control unsuccessful. Switch power off.
If fault persists, contact your
nearest ACS 300 supplier.
Fault indication Possible cause Remedy