ACS 300 User’s Manual 7
Chapter 1 - Overview of This Manual
Type Series
Table 1-1 and Table 1-2 list the principal input and output rat-
ings for each of the various ACS 300 type designations. The
frame size assignments R0, R1 and R2 are used to identify
the enclosure sizes and other characteristics of the various
models.
Table 1-1 ACS 300 AC drive types for 50 Hz and 60 Hz supplies.
Input power supply 200 to 240 V.
1)
Allowed for one minute every ten minutes at 50°C ambient.
2)
The impedance of input power supply affects the input current.
3)
The single underline (_) in the type designation
stands for “0” or “1”.
Type
designation
3)
Frame
Rated input
current
2)
Output current
Maximum
permissible
rated motor
power
Weight
1-phase
I
1
[A]
3-phase
I
1
[A]
Rated
current
I
N
[A]
Short-term
overload
current
I
OVER
[A]
1)
P
N
[Hp]
P
N
[kW]
[lbs.] [kg]
ACS 311-1P1-1 R0 6.6 - 3.0 4.5 1/2 0.55 6.8 3.1
ACS 311-1P6-1 R0 8.9 - 4.3 6.5 1 0.75 6.8 3.1
ACS 301-2P1-1 R1 12.2 - 5.5 8.3 1-1/2 1.1 10.1 4.6
ACS 311-2P1-1 R1 12.2 8.4 5.5 8.3 1-1/2 1.1 10.1 4.6
ACS 301-2P7-1 R1 15.7 - 7.1 10.7 2 1.5 10.1 4.6
ACS 311-2P7-1 R1 15.7 9.8 7.1 10.7 2 1.5 10.1 4.6
ACS 301-4P1-1 R1 22.4 - 10.7 13.0 3 2.2 10.1 4.6
ACS 311-4P1-1 R1 22.4 12.9 10.7 13.0 3 2.2 10.1 4.6