36 ACS 300 User’s Manual
Chapter 5 - Start-up
Checking the
Parameters
The parameter tables starting on page 45 provide a brief
description of each parameter and include a space to write
down your customized settings. For each parameter, the
table lists the page number on which a detailed explanation
of the parameter can be found.
Start-up data
Before proceeding with the commissioning, check and com-
plete the following Page 1 and Page 4 parameters which
define the motor connected to the ACS 300 and input power
supply (400 V series only):
NOM RPM = Nominal motor speed Code 113
2NOM RPM = Nominal motor speed Code 803
NOM FREQ = Nominal motor frequency Code 114
2NOM FREQ = Nominal motor frequency Code 804
NOM VOLT = Nominal motor voltage Code 115
2NOM VOLT = Nominal motor voltage Code 805
COS PHI = Cos phi of the motor Code 116
2COS PHI = Cos phi of the motor Code 806
SUPPLY VOLT = Supply voltage Code 117
(400 V series only)
Note! Supply voltage (SUPPLY VOLT) should be set before
setting the nominal voltage of the motor (NOM VOLT). Refer
to the detailed descriptions of these parameters in Chapter 7
on page 51.
Note! The page 4 settings (2NOM RPM, 2NOM FREQ,
2NOM VOLT and 2COS PHI) should be set to match the
corresponding page 1 settings unless special application cir-
cumstances require 2 sets of motor characteristic settings.