28 ACS 300 User’s Manual
Chapter 4 - Control Connections
Standard
The ACS 300 comes from the factory preset to standard.
Table 4-1 shows the functions of the digital inputs in standard
mode.
Table 4-1 Standard digital input functions.
Figure 4-3 Standard switch S1 selection.
Table 4-2 Constant speed selection.
Digital input Function Notes
DI1 Start / Stop Connect +24 V DC to start
DI2 Reverse Connect +24 V DC to reverse
DI3 CS Constant speed (= CS) selection,
refer to table 4-2
DI4 CS
DI5 ACC2/DEC2 0 V = ramp1 and +24 V DC = ramp2
DI3 DI4 Result
0 0 Speed reference from AI1
+24 V 0 Constant speed 1
0 +24 V Constant speed 2
+24 V +24 V Constant speed 3
OFF
ON
0
1
Standard (Default)