EasyManua.ls Logo

ABB ACS 311-1P6-1 - Page 93

ABB ACS 311-1P6-1
101 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ACS 300 User’s Manual 79
Chapter 8 - Fault Tracing
Table 8-1 Fault tracing.
Fault indication Possible cause Remedy
(1) NO FAULT This message only appears in the
fault memory.
(2) OVERVOLTAGE DC bus voltage has exceeded
130 % nominal voltage. Overvolt-
age is generally caused when the
motor runs as a generator in
drives where the load inertia is
high and the deceleration time is
set low. Too high mains voltage
may also be the cause.
In case of temporary supply
voltage peak, reset and start.
Use longer deceleration time or
Use coasting stop function if it
is compatible with the applica-
tion.
If short deceleration time is
needed, use external Braking
options.
Check supply voltage (400 V)
(3) UNDERVOLTAGE DC bus voltage has gone below
65 % of the nominal voltage. Most
common reason for low voltage
trip is failure in the mains supply,
loss of phase or “brown out” con-
dition.
In case of temporary supply
voltage drop, reset and start.
Check mains input.
(4) OVERCURRENT Motor may be too small for the
application.
Motor current is too high due to
high load inertia/short ramp
times
sudden load torque change
stalling motor
motor cabling or motor failure
long motor cable
Check ramp times
Remove mechanical problem
causing increased load torque.
Check cables and motor
Use optional output chokes
Check dimensioning, use
larger ACS 300 and motor if
necessary.
(5) LOW AI-SIGNAL Analogue input less than 2 V/4mA
and minimum has been set to
2 V/4 mA or Analogue Input less
than selected “customised
minimum”.
Input reference has failed or
control cable is broken. Check
the reference circuit.

Related product manuals