58 ACS 400 Users Manual
Application Macro Alternate
This macro offers an I/O configuration that is adopted to a sequence of DI control signals used
when alternating the direction of rotation of the drive.
The value of parameter 9902 is 3 (
ALTERNATE).
*Constant speed selection: 0 = open, 1 = connected
Application macro Alternate parameter values:
Input signals Output signals Jumper Setting
Start, stop and direction
(DI1,2)
An. output AO: Frequency
Analog reference (AI1) Relay output 1: Fault
Preset speed selection (DI3,4) Relay output 2: Running
Ramp pair 1/2 selection (DI5)
DI3 DI4 Output
00Reference through AI1
10Constant speed 1 (1202)
01Constant speed 2 (1203)
11Constant speed 3 (1204)
1001
EXT 1 COMMANDS 9 (DI1F,2R) 1402 RELAY OUTPUT 22 (RUN)
1002
EXT 2 COMMANDS 0 (NOT SEL) 1503 AO CONTENT MAX 60 Hz
1003
DIRECTION 3 (REQUEST) 1601 RUN ENABLE 0 (NOT SEL)
1102
EXT1/EXT2 SEL 6 (EXT1) 1604 FAULT RESET SEL 0 (KEYPAD)
1103
EXT REF1 SELECT 1 (AI1) 2008 MAXIMUM FREQ 60 Hz
1105
EXT REF1 MAX 60 Hz 2105 PREMAGN SEL 0 (NOT SEL)
1106
EXT REF2 SELECT 0 (KEYPAD) 2201 ACC/DEC 1/2 SEL 5 (DI5)
1201
CONST SPEED SEL 7 (DI3,4) 4001 PID GAIN 1.0
1401
RELAY OUTPUT 13 (FAULT (-1)) 4002 PID INTEG TIME 60 s
External Reference 1: 0...10 V <=> 0...50 Hz
Reference voltage 10 VDC
Not used
Output frequency 0...20 mA <=> 0...50 Hz
+24 VDC
Start fwd: If DI1 state is the same as DI2, drive stops
Start reverse
Constant Speed selection*
Constant Speed selection*
Ramp pair selection. Activate to select ramp pair 2.
Relay output 1, programmable
Default operation: Fault =>17 connected to 18
Relay output 2, programmable
Default operation: Running =>20 connected to 22