2)
Description
Term.
1)
Connection
Digital inputs and auxiliary voltage output
×
Aux. voltage output +24 V DC, max. 250 mA
3)
+24V
+24 V
DGND
DCOM
DI1
DI2
DI3
DI4
DI5
DI6
+24 V
DGND
DCOM
DI1
DI2
DI3
DI4
DI5
DI6
×Aux. voltage output commonDGND
×Digital input common for allDCOM
×Stop (0) / Start (1)DI1
×Forward (0) / Reverse (1)DI2
Constant output frequency selection
4)
DI3
Constant output frequency selectionDI4
Ramp set 1 (0) / Ramp set 2 (1)
5)
DI5
Not configuredDI6
Relay outputs
Aux. voltage output +24 V DC, max. 250 mA
3)
+24V
RO2C
RO2A
RO2B
RO3C
RO3A
RO3B
RO1C
RO1A
RO1B
+24 V
DGND
DCOM
+24 V
DGND
DCOM
Aux. voltage output commonDGND
Digital input common for allDCOM
×Ready run
250 V AC / 30 V DC, 2 A
CommonRO1C
×Norm. closedRO1A
×Norm. openRO1B
Running
250 V AC / 30 V DC, 2 A
CommonRO2C
Norm. closedRO2A
Norm. openRO2B
Fault (-1)
250 V AC / 30 V DC, 2 A
CommonRO3C
Norm. closedRO3A
Norm. openRO3B
Embedded EIA-485
Embedded fieldbus (EIA-485)B+
B+
A-
DGND
A-
DGND
Termination switch. ON = on. 1 = off.TERM
Safe torque off
×Safe torque off. Factory connection. Both circuits must be
closed for the drive to start.
SGND
OUT1
SGND
IN1
IN2
×IN1
×IN2
×OUT1
Auxiliary voltage input/output
Aux. voltage output +24 V DC, max. 250 mA
3)
+24V
+24 V
DGND
DCOM
Aux. voltage output commonDGND
Digital input common for allDCOM
1)
Terminal size: 0.14…1.5 mm
2
(26…16 AWG) Tightening torque: 0.5 N·m (0.4 lbf·ft)
2)
× = base unit, empty = RIIO-01 module
3)
The sum output current from 24 V terminals of base unit and RIIO-01 module must not exceed 250 mA.
Electrical installation North America 77