Installation instructions 81
2. Twist the cable shields of the motor cables into bundles and connect them and any
separate ground conductors or cables to the grounding terminal of the drive module.
3. Connect the phase conductors of the motor cables to terminals T1/U2, T2/V2 and
T3/W2 of the drive module. For the tightening torques, see page 118.
4. Make sure that all power is disconnected and reconnection is not possible. Use proper
safe disconnect procedures according to local codes.
5. Run the input cables from the supply source to the cabinet. If shielded cable is used
:
we recommend to ground the cable shields 360° at the lead-through plate.
6. If shielded cable is used
: twist the cable shields of the input cables into bundles and
connect them and any separate ground conductors or cables to the drive module
grounding terminal.
7. Connect the phase conductors of the input cables to terminals L1/U1, L2/V1 and
L3/W1 of the drive module. For the tightening torques, see page 118.
DC connection
The UDC+ and UDC– terminals are intended for common DC configurations of a number
of drives, allowing regenerative energy from one drive to be utilized by the other drives in
the motoring mode. For more information, contact your local ABB representative.