202 ACS550 User’s Manual
Diagnostics
4 SHORT CIRC Fault current. Check for and correct:
A short-circuit in the motor cable(s) or motor.
Supply disturbances.
5 Reserved Not used.
6
DC UNDERVOLT Intermediate circuit DC voltage is not sufficient. Check for and correct:
Missing phase in the input power supply.
Blown fuse.
Undervoltage on mains.
7
AI1 LOSS Analog input 1 loss. Analog input value is less than AI1FLT LIMIT (3021).
Check for and correct:
Source and connection for analog input.
Parameter settings for
AI1FLT LIMIT (3021) and 3001 AI<MIN FUNCTION.
8
AI2 LOSS Analog input 2 loss. Analog input value is less than AI2FLT LIMIT (3022).
Check for and correct:
Source and connection for analog input.
Parameter settings for AI2FLT LIMIT (3022) and 3001 AI<MIN FUNCTION.
9 MOT TEMP Motor is too hot, based on either the drive’s estimate or on temperature
feedback.
Check for overloaded motor.
Adjust the parameters used for the estimate (3005…3009).
Check the temperature sensors and Group 35 parameters.
10
PANEL LOSS Panel communication is lost and either:
Drive is in local control mode (the control panel displays LOC), or
Drive is in remote control mode (REM) and is parameterized to accept
start/stop, direction or reference from the control panel.
To correct check:
Communication lines and connections
Parameter 3002
PANEL COMM ERROR.
Parameters in Group 10: Command Inputs and Group 11: Reference
Select (if drive operation is REM).
11
ID RUN FAIL The motor ID Run was not completed successfully. Check for and correct:
Motor connections
Motor parameters 9905…9909
12
MOTOR STALL Motor or process stall. Motor is operating in the stall region. Check for and
correct:
Excessive load.
Insufficient motor power.
Parameters 3010…3012.
13 RESERVED Not used.
14 EXTERNAL FLT 1 Digital input defined to report first external fault is active. See parameter
3003
EXTERNAL FAULT 1.
15 EXTERNAL FLT 2 Digital input defined to report second external fault is active. See parameter
3004
EXTERNAL FAULT 2.
Fault
Code
Fault Name In
Panel
Description and Recommended Corrective Action