Typical power cable sizes
US
IEC
1)
FramesizeDrive type
ACS560
AI cable
type
3)
Cu cable type
AI cable
type
2)
Cu cable type
AWG/kcmilAWG/kcmilmm
2
mm
2
3-phase U
N
= 400 V (380…480 V)
-16-3 × 1.5 + 1.5R002A6-4
-16-3 × 1.5 + 1.5R003A3-4
-16-3 × 1.5 + 1.5R004A0-4
-16-3 × 1.5 + 1.5R005A6-4
-16-3 × 1.5 + 1.5R007A2-4
-14-3 × 2.5 + 2.5R009A4-4
-14-3 × 2.5 + 2.55R112A6-4
-14-3 × 2.5 + 2.5R2017A-4
-10-3 × 6 + 6R2025A-4
-8-3 × 10 + 10R3033A-4
-8-3 × 10 + 10R3039A-4
-6-3 × 16 + 16R3046A-4
-43 × 353 × 25 + 16R4062A-4
-23 × 503 × 35 + 16R4073A-4
-23 × 703 × 35 + 16R5088A-4
-1/03 × 703 × 50 + 25R5106A-4
-3/03 × 1203 × 95 + 50R6145A-4
-250 MCM3 × 1503 × 120 + 70R7169A-4
-300 MCM3 × 2403 × 150 + 70R7206A-4
-2 × 2/02 × (3 × 95)2 × (3 × 70 +
35)
R8246A-4
-2 × 3/02 × (3 × 120)2 × (3 × 95 +
50)
R8293A-4
1)
The cable sizing is based on maximum parallel layout of 6 cables laid on a cable ladder side by side,
ambient temperature 30 °C, PVC insulation, surface temperature 70 °C (EN 60204-1 and IEC
60364-5-52/2001). For other conditions, size the cables according to local safety regulations, appropriate
input voltage and the load current of the drive.
2)
Aluminum cables must not be used with frames R0…R4.
3)
In the USA, aluminum cables must not be used.
Technical data 131