What to doCauseFault / Aux.
code aux code
visible only on
assistant con-
trol panel and
drive com-
poser))
Code
(hex)
Check the load.Underload occurred
between speed point
37.14 ULC speed table
point 4 and 37.15 ULC
speed table point 5.
004
See parameter 37.03 ULC overload
actions.
User load curve: Signal has
been too long over the
overload curve.
ULC overload
fault
8002
Check the load.Overload occurred
between speed point 37.11
ULC speed table point 1
and 37.12 ULC speed table
point 2.
001
Check the load.Overload occurred
between speed point 37.12
ULC speed table point 2
and 37.13 ULC speed table
point 3.
002
Check the load.Overload occurred
between speed point 37.13
ULC speed table point 3
and 37.14 ULC speed table
point 4.
003
Check the load.Overload occurred
between speed point
37.14 ULC speed table
point 4 and 37.15 ULC
speed table point 5.
004
Reduce the motor load. Check for
any jam or stall in motor. See para-
meter 30.17 Maximum current.
Motor actual current ex-
ceeded the limit defined
in parameter 30.17 Maxim-
um current.
Current limit8009
Check signal level, auxiliary code,
wiring connected to the input and
the minimum/maximum limits of
the input in parameter group 12
Standard AI.
An analog signal is out-
side the limits specified
for the analog input.
AI supervision80A0
166 Diagnostics