What to doCauseFault / Aux.
code aux code
visible only on
assistant con-
trol panel and
drive com-
poser))
Code
(hex)
Check safety circuit connections
and parameter 95.04 Control board
supply.
Safe torque off function
is active, ie. STO circuit 1
is broken.
Safe torque off 1FA81
Safe torque off function
is active, ie. STO circuit 2
is broken.
Safe torque off 2FA82
CheckMotor ID run was not
completed successfully.
ID runFF61
nominal motor values in para-
meter group 98 User motor
parameters.
that no external control system
is connected to the drive.
that no operation limits prevent
the completion of the ID run.
Restore parameters to default
settings and try again.
that the motor shaft is not
locked.
Cycle the power to the drive (and
its control unit, if powered separ-
ately).
168 Diagnostics