What to doCauseFault / Aux.
code aux code
visible only on
assistant con-
trol panel and
drive com-
poser))
Code
(hex)
B - (Asynchronous motors only) Speed
dropped to zero during ID run.
1 - Maximum current limit too low
C - (Permanent magnet motors only).
First acceleration did not finish within
reasonable time.
2 - Maximum speed limit or calculated
field weakening point too low
D - (Permanent magnet motors only).
Second acceleration did not finish
within reasonable time.
3 - Maximum torque limit too low
E...10 - Internal error4 - Current measurement calibration
not finished within reasonable time
11 - (Synchronous reluctance motors
only). Pulse test error.
5...8 - Internal error
12 - Motor too large for advanced
standstill ID run.
9 - (Asynchronous motors only). Accel-
eration not finished within reasonable
time.
13 - (Asynchronous motors only). Motor
data error.
A - (Asynchronous motors only) .Decel-
eration not finished within reasonable
time.
Reboot the control unit (using
parameter 96.08 Control board
boot or by cycling power.
SW internal malfunction.STO diagnostics
failure.
FF63
Check the fault information
provided by the PLC.
A fault trip command
through fieldbus adapter
A.
FB A force tripFF81
Check the fault information
provided by the PLC.
A fault trip command
through embedded field-
bus interface.
EFB force tripFF8E