142 Maintenance and hardware diagnostics
Description of symbols
Recommended annual actions by the user
Recommended maintenance actions by the user
Action Description
I Inspection (visual inspection and maintenance action if needed)
P Performance of on/off-site work (commissioning, tests, measurements or
other work)
R Replacement
Action Description
P Quality of supply voltage
I Spare parts
P Capacitor reforming for spare drives and spare capacitors (page 154)
I Tightness of terminals
I Dustiness, corrosion or temperature
P Heat sink cleaning (page 143)
Component Years from start-up
3 6 9 12 15 18 21
Cooling
Fans, IP21 (UL Type 1) frames R1 to R9
Main cooling fan
R1…R4: page 145, R5: page 147
RRR
Main cooling fan LONGLIFE
R6…R8: page 147, R9: page 148
RR
Auxiliary cooling fan (LONGLIFE) for circuit boards, R5…R9:
page 149
RR
Fans, IP55 (UL Type 12) frames R1 to R9
Main cooling fan
R1…R4: page 145, R5: page 147
RRR
Main cooling fan LONGLIFE
R6…R8: page 147, R9: page 148
RR
Auxiliary cooling fan for circuit boards
R1…R2
1)
: page 150
RRR
Auxiliary cooling fan (LONGLIFE) for circuit boards
R3: page 151, R4: page 152, R5…R9: page 149
RR
Second auxiliary cooling fan (LONGLIFE) R8 and R9: page 153 RR
Aging
Control panel battery: page 155 RR
4FPS10000309652.xlsx H
1)
Valid for ACS580-01 type codes listed in this manual. For other type codes, see ACS580-01 (0.75 to 250
kW, 1.0 to 350 hp) hardware manual (3AXD50000018826 [English]).