170 Technical data
uR and aR fuses
Type
ACS580
-01-
Min. short-
circuit
current
1)
Input
current
uR or aR
Nominal
current
I
2
t Vo ltage
rating
Bussmann
type
IEC 60269
size
A A A A
2
s V
3-phase U
N
= 400 or 480 V (380…415 V, 440…480 V)
02A7-4 65 2.6 25 130 690 170M1561 000
03A4-4 65 3.3 25 130 690 170M1561 000
04A1-4 65 4.0 25 130 690 170M1561 000
05A7-4 65 5.6 25 130 690 170M1561 000
07A3-4 65 7.2 25 130 690 170M1561 000
09A5-4 65 9.4 25 130 690 170M1561 000
12A7-4 65 12.6 25 130 690 170M1561 000
018A-4 120 17.0 40 460 690 170M1563 000
026A-4 120 25.0 40 460 690 170M1563 000
033A-4 170 32.0 63 1450 690 170M1565 000
039A-4 170 38.0 63 1450 690 170M1565 000
046A-4 280 45.0 80 2550 690 170M1566 000
062A-4 380 62 100 4650 690 170M1567 000
073A-4 480 73 125 8500 690 170M1568 000
088A-4 480 88 160 16000 690 170M1569 000
106A-4 700 106 200 15000 690 170M3815 1
145A-4 700 145 250 28500 690 170M3816 1
169A-4 1280 169 315 46500 690 170M3817 1
206A-4 1520 206 350 68500 690 170M3818 1
246A-4 2050 246 450 105000 690 170M5809 2
293A-4 2200 293 500 145000 690 170M5810 2
363A-4 3100 363 630 275000 690 170M5812 2
430A-4 3600 430 700 405000 690 170M5813 2
3AXD00000586715.xls J
1)
Minimum short-circuit current of the installation