Technical data 179
Frame
size
Cable lead-
throughs
R+, R-, UDC+ and UDC- terminals
Per cable
type
Ø
1)
Min wire size
(solid/
stranded)
3)
Max wire size
(solid/
stranded)
T (Wire screw)
pcs mm mm
2
mm
2
M… N·m
R1 1 23 0.20/0.25 6/4
2)
1.2…1.5
R2 1 23 0.5/0.5 16/16
2)
1.2…1.5
R3 1 23 0.5/0.5 35/25
2)
2.5…4.5
R4 1 39 0.5/0.5 50
2)
4.0
R5 1 39 6 70 M5 5.6
R6 1 45 25 150 M8 30
R7 1 54 95 240 M10 30
R8 2 45 2×50 2×150 M10 40
R9 2 54 2×95 2×240 M12 70
3AXD00000586715.xls J
1)
Maximum cable diameter accepted. For the lead-through plate hole diameters, see chapter
Dimension drawings on page 203.
2)
See the table below.
3)
Note: Minimum wire size does not necessarily have enough current capability for full load.
Make sure the installation complies with local laws and regulations.
Frame
size
Screwdrivers for the terminals of the main circuit
R1 Combo: Slot 4 mm and PH1
R2 Combo: Slot 4.5 mm and PH2
R3, R4 PH2
3AXD00000586715.xls J