EasyManua.ls Logo

ABB ACS580-01 - Page 255

ABB ACS580-01
278 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Optional I/O extension modules 255
Isolation areas:
Relay outputs (50…52, 53…55):
Wire size max. 1.5 mm
2
Minimum contact rating: 12 V / 10 mA
Maximum contact rating: 250 V AC / 30 V DC / 2 A
Maximum breaking capacity: 1500 VA
115/230 V inputs (70…78):
Wire size max. 1.5 mm
2
Input voltage: 115 to 230 V AC ±10%
Maximum current leakage in digital off state: 2 mA
Symbol Description
Reinforced insulation (IEC 61800-5-1:2007)