88 Planning the electrical installation
The table shows what temperature sensor types you can connect to the drive I/O
extension modules as well as the insulation requirement for the sensor.
Extension module Temperature sensor type
Type Insulation PTC KTY Pt100,
Pt1000
CMOD-02 Reinforced insulation between the motor
thermistor connector and the other
connectors of the module (including drive
control unit connector).
> No special requirements for the
thermistor insulation level.
(The drive control board is PELV
compatible also when the module and a
thermistor protection circuit are installed.)
X- -
CPTC-02 X - -