Update notice 1
Update notice
Safety
ADDED:
Before you activate the automatic fault reset or automatic restart functions of the drive
control program, make sure that no dangerous situations can occur. These functions
reset the drive automatically and continue operation after a fault or supply break. If
these functions are activated, the installation must be clearly marked as defined in
IEC/EN 61800-5-1, subclause 6.5.3, for example, "THIS MACHINE STARTS
AUTOMATICALLY".
If bypassing is required, employ mechanically or electrically interlocked contactors
between the motor and the drive and between the motor and the power line. Make
sure with interlocking that the contactors cannot be closed simultaneously. The
installation must be clearly marked as defined in IEC/EN 61800-5-1, subclause 6.5.3,
for example, "THIS MACHINE STARTS AUTOMATICALLY".
Default I/O connection diagram
CHANGED:
11. Internal overtemperature supervision of the cabinet is connected between DI6 and +24V aux. voltage
supply. If DI6 is to be used for another purpose, see section Changing internal overtemperature supervision
from DI6 to another digital input on page 2.
This notice concerns ACS580-07 hardware manual
(3AXD50000032622 [English]) Rev A.
Code: 3AXD50000131464 Rev A
Valid: from 2.6.2017 until the release of revision
B of the manual.
Contents: new or changed instructions
Auxiliary voltage output
10 +24V Auxiliary voltage output +24 V DC, max. 250 mA
4)
11 DGND Auxiliary voltage output common
12 DCOM Digital input common for all
Programmable digital inputs DI1…DI3
13 DI1 Stop (0) / Start (1)
14 DI2 Forward (0) / Reverse (1)
15 DI3 Constant frequency/speed selection
6)
Programmable digital inputs DI4…DI6
16 DI4 Constant frequency/speed selection
6)
17 DI5
Ramp set1 (0) / Ramp set 2 (1)
7)
18 DI6 Internal overtemperature supervision. 0 = Fault
Relay outputs
19 RO1C Ready run
250 V AC / 30 V DC
2 A
20 RO1A
21 RO1B
22 RO2C Running
250 V AC / 30 V DC
2 A
23 RO2A
24 RO2B
25 RO3C Fault (-1)
250 V AC / 30 V DC
2 A
26 RO3A
27 RO3B
EIA/5-485
8)
10)
11)
X504:10
X504:
18