92 Start-up
Start-up with the First start assistant on an assistant panel
This section describes the start-up of the drive using the First start assistant on the
assistant control panel.
Complete documentation of the drive firmware: program features, parameters and fault
tracing can be found in ACS580 firmware manual (3AXD50000016097 [English]). For
more information on the assistant panels, see ACS-AP-x Assistant control panels user’s
manual (3AUA0000085685 [English]).
Setting up the drive parameters, and performing the first start
Setup the drive control program. See section Start-up with the First start assistant on an assistant
panel on page 92.
Drives with main contactor (Q2, option +F250):
Close the main contactor by turning the operating
switch on the cabinet door from OFF into ON position.
Perform the first start of the drive and motor.
Stop the motor and drive.
Drives with with a fieldbus adapter module (optional):
Set the fieldbus parameters. Activate the
appropriate assistant in the control program, or see the user’s manual of the fieldbus adapter module,
and the drive firmware manual. Not all control programs include assistants.
Check that the communication works between the drive and the PLC.
On-load checks
Check that the cooling fans rotate freely in the right direction, and the air flows upwards. A paper
sheet set on the intake (door) gratings stays. The fans run noiselessly.
Check that the motor starts. stops and follows the speed reference in right direction when controlled
with the control panel.
Check that the motor starts. stops and follows the speed reference in right direction when controlled
through the customer-specific I/O or fieldbus.
Drives in which the Safe torque off control circuit is connected:
Test and validate the operation of the
Safe torque off function. Start-up including acceptance test on page 143.
Drives with an emergency stop circuit (options +Q951):
Test and validate the operation of the
emergency-stop circuit. See the delivery specific circuit diagrams and wiring, start-up and operating
instructions of the option (see page 59).
Safety
Make sure that the installation work is complete. Make sure that the cabinet door is closed.
Check that the starting of the motor does not cause any danger. De-couple the driven
machine if there is a risk of damage in case of an incorrect direction of rotation.
Action