ABB ACS580-07 - Option +E205 in Frames R10 and R11: DI6 Internal Overtemperature Supervision; Power Supply Connections for PNP with Option +L504

ABB ACS580-07
288 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2. Total load capacity of the Auxiliary voltage output +24V (X2:10) is 6.0 W (250 mA / 24 V)
minus the power taken by the option modules installed on the board.
3. In scalar control (default): See Menu - Primary settings - Start, stop, reference -
Constant frequencies or parameter group 28 Frequency reference chain.
In vector control: See Menu - Primary settings - Start, stop, reference - Constant
speeds or parameter group Speed reference selection
Operation/ParameterDI4DI3
Set frequency through AI100
28.26 Constant frequency 101
28.27 Constant frequency 210
28.28 Constant frequency 311
4. See Menu - Primary settings - Ramps or parameter group 28 Frequency reference
chain.
ParametersRamp setDI5
28.72 Freq acceleration time 110
28.73 Freq deceleration time 1
28.74 Freq acceleration time 221
28.75 Freq deceleration time 2
5. Connected with jumpers at the factory.
6. Ground the outer shield of the cable 360 degrees under the grounding clamp on the
grounding shelf for the control cables.
7. With option +E202 in frames R10 and R11, digital input DI6 is reserved for internal
overtemperature supervison of the cabinet. See section Option +E205 in frames R10
and R11: DI6 internal overtemperature supervision (page 118)
Option +E205 in frames R10 and R11: DI6 internal overtemperature
supervision
With option +E205, digital input DI6 is used by default for the internal overtemperature
supervision of the cabinet in frames R10 and R11. The I/O connection is shown below.
X4
*)
X2 & X3
10 +24V
11 DGND
12 DCOM
13 DI1
14 DI2
15 DI3
16 DI4
17 DI5
18 DI6
*) Internal overtemperature supervision of the cabinet is connected between DI6 and +24V
auxiliary voltage supply. If DI6 is to be used for another purpose, see section Changing
internal overtemperature supervision from DI6 to another digital input (page 120)
Power supply connections for PNP with option +L504
Internal and external +24 V power supply connections with option +L504 for PNP
configuration are shown below.