Loading...
PNP connection (source)
X503:1
X504:18
+24 V DC
0VDC
PNP connection (source)
10 +24V
11 DGND
12 DCOM
13 DI1
14 DI2
15 DI3
16 DI4
17 DI5
18 DI6
X504:18
X503:1
10 +24V
11 DGND
12 DCOM
13 DI1
14 DI2
15 DI3
16 DI4
17 DI5
18 DI6
Inter
nal +24 V power supply External +24 V power supply
Power supply connections for NPN with option +L504
Internal and external +24 V power supply connections for NPN configuration are shown
below.
Internal +24 V power supply External +24 V power supply
NPN connection (sink)
X503:1
10 +24V
11 DGND
12 DCOM
13 DI1
14 DI2
15 DI3
16 DI4
17 DI5
18 DI6
NPN connection (sink)
10 +24V
11
DGND
12 DCOM
13 DI1
14 DI2
15 DI3
16 DI4
17 DI5
18 DI6
0VDC
+24 V DC
X504:18
X503:1
X504:18
Power supply connections for PNP without option +L504
Internal and external +24 V power supply connections without option +L504 for PNP
configuration are shown below.
PNP connection (source)
X4
+24 V DC
0VDC
PNP connection (source)
10 +24V
11 DGND
12 DCOM
13 DI1
14 DI2
15 DI3
16 DI4
17 DI5
18 DI6
X4
10 +24V
11 DGND
12 DCOM
13 DI1
14 DI2
15 DI3
16 DI4
17 DI5
18 DI6
Internal +2
4 V power supply External +24 V power supply
Power supply connections for NPN without option +L504
Internal and external +24 V power supply connections without option +L504 for NPN
configuration are shown below.
Control unit 119