13. Install the new module in reverse order.
Replacing the drive module (frames R10 and R11, IP54)
WARNING!
Obey the instructions in chapter Safety instructions. If you ignore them, injury or
death, or damage to the equipment can occur.
This replacing procedure requires: preferably two persons, installation ramp, a set of screw
drivers and a torque wrench with an extension bar of 500 mm (20 in), chains for securing
the module during the installation.
The drawings show frame R10. The details in frame R11 are slightly different.
1.
Stop the drive and do the steps in section Electrical safety precautions (page 20) before
you start the work.
2. Open the cabinet door.
3. Remove the shrouds and the additional IP54 fan.
4. Unplug the quick connectors at the top and bottom of the control unit mounting plate.
5. Disconnect the PE conductor of the auxiliary control voltage transformer.
6. Remove the mounting plate.