13. Install the new module in reverse order.
Capacitors
The DC circuit of the power modules of the drive contain several electrolytic capacitors.
Their lifespan depends on the operating time of the drive, loading and ambient temperature.
Capacitor life can be prolonged by lowering the ambient temperature.
Capacitor failure is usually followed by damage to the unit and an input cable fuse failure,
or a fault trip. Contact ABB if capacitor failure is suspected. Replacements are available
from ABB. Do not use other than ABB specified spare parts. Contact an ABB service
representative for spare parts and repair services.
■ Reforming the capacitors
The capacitors must be reformed if the drive has not been powered (either in storage or
unused) for a year or more. The manufacturing date is on the type designation label. For
information on reforming the capacitors, see Converter module capacitor reforming
instructions (3BFE64059629 [English]) in the ABB Library (https://library.abb.com/en).
If the drive module has been stored for one to three years, turn on the mains power for 30
minutes without load, then continue as usual.
If the drive module has been stored for less than a year, continue as usual.
Fuses
■ Replacing AC fuses (frames R6 and R7)
WARNING!
Obey the instructions in chapter Safety instructions. If you ignore them, injury or
death, or damage to the equipment can occur.
166 Maintenance