ABB ACS580-07 - Drive Types ACS580-0414 A-4 and ACS580-0430 A-4; Altitude Derating

ABB ACS580-07
288 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
T
1.00
0.90
+40 °C
+104 °F
+50 °C
+122 °F
k
0.80
For example:
Derated currentTemperature
I
Hd
I
Ld
40 ºC (104 ºF)
0.95 · I
d
0.95 · I
Ld
45 ºC (113 ºF)
0.90 · I
Hd
0.90 · I
Ld
50 ºC (122 ºF)
Drive types ACS580-0414A-4 and ACS580-0430A-4
In the temperature range +35…50 °C (+95…122 °F), the rated output current is derated by
1% for every added 1 °C (1.8 °F). The output current can be calculated by multiplying the
current given in the rating table by the derating factor (k):
T
1.00
0.90
+40 °C
+104 °F
+50 °C
+122 °F
k
0.80
+35 °C
+95 °F
0.85
0.95
Altitude derating
At altitudes from 1000 to 2000 m (3300 to 6561 ft) above sea level, the derating is 1% for
every 100 m (328 ft). Multiply the output current given in Ratings (page 171) by the coefficient
value given in this table.
CoeffficientFrame
4000 m
13123 ft
3000 m
9842 ft
2000 m
6562
1000 m
3281 ft
0.700.800.901.00R6
0.700.800.901.00R7
0.700.800.901.00R8
0.700.800.901.00R9
0.700.800.901.00R10
174 Technical data